Home > Hardware > CAN-Gateways >
DeviceNet Profibus-DP Gateway
DN-DP
Item #: C.2930.02
Availability: Call For Pricing - (413) 772-3170
Usually ships In 2 Weeks
DN-DP
Profibus-DP / DeviceNet Gateway
- Fast and reliable linking Profibus-DP and DeviceNet with data buffering
- DeviceNet-PLC link, e.g. to SIEMENS S7-300 or S7-400
Linking DP and DeviceNet
The module DN-DP can link any Profibus-DP master to a DeviceNet network. The DN-DP gateway operates
as a slave-I/O component with a total of maximum 312 bytes data (partitioning from up to 244 bytes
input and 68 bytes output to 244 bytes output and 68 bytes input data) on the DP-bus. At the
DeviceNet, the DN-DP can operate as a scanner or as a slave device.
Applications
With the DN-DP gateway, you can couple DeviceNet modules to e.g. a SIMATIC-S7. The module does not
limit the number of DeviceNet participants.
Physical Interfaces
The DN-DP supports all DeviceNet compatible bitrates The Profibus-DP-Slave interface automatically
recognizes all usual bit rates up to 12 Mbit/s. The DP as well as the DeviceNet interface are
electrically isolated.
Configuration
Configuration is possible via a PROFIBUS configuration tool, e.g. the PLC SIMATIC Manager.
Technical Specifications:
CPU:
|
Microcontroller:
|
PowerPCTM 405 EP, 133 MHz
|
Memory:
|
4 M x 32 bit SDRAM (16 MB), 512 k x 16 bit Flash EPROM
(1 MB)
|
DeviceNet:
|
CAN controller:
|
SJA1000, ISO11898-1 (CAN 2.0)
|
DeviceNet interface:
|
According to DeviceNet Specification release 2.0,
differential, electrically isolated, all DeviceNet bit rates are supported
|
PROFIBUS-DP:
|
DP controller:
|
VPC3, DP-Slave
|
DP interface:
|
RS-485, electrically isolated, max. 12 Mbit/s
|
General:
|
Operating voltage:
|
Nominal 24 VDC
|
Connectors:
|
DeviceNet: 5-pole socket connector
DP: 9-pole female DSUB
Power: 4-pole spring force connection plug
|
Order information:
Designation
|
|
Order no.
|
DN-DP
|
DeviceNet-DP gateway ISO11898-2, GSD-file
|
C.2930.02
|
DN-DP-ME
|
English user manual
|
C.2930.21
|